5-27
Chapter 5. SETTINGS BEFORE STARTING OPERATION
CT wait time before measurement setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) In the parameter setting display mode, keep the [para]
key pressed for 2 s or longer.
>>
The display is then changed to the setup setting
display.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [para] key several times.
>>
Display the setup setting [C38: CT1 wait time
before measurement].
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(4) Press the [<], [
], or [
] key to change the set value in
[C38].
Setting range: 30 to 300 ms
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(5) Press the [mode] key.
>>
The display is returned to the operation display.
Handling Precautions
• The display of [CT2 wait time before measurement] is [C41].
• When the optional function of the model is that CT is not provided, [C38]
and [C41] are not displayed.
When [C36] is set at [1: Current measurement], [C38] is not displayed.
When [C39] is set at [1: Current measurement], [C41] is not displayed.