6-8
Chapter 6. SETTINGS DURING OPERATION
RUN/READY mode selection setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) In the parameter setting display mode, press the
[para] key.
>>
The parameter setting [r--r:RUN/READY mode
selection] is displayed.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [
], or [
] key to set the value you have
selected from the following in [r--r].
rUn: RUN mode
rdy: READY mode
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
>>
The display is returned to the operation display.
Handling Precautions
When the operation type of any of internal contacts 1 to 3 is set at “RUN/
READY mode selection”, [r--r] cannot be changed.