6-13
Chapter 6. SETTINGS DURING OPERATION
I-1 (Integration time) setup
(1) In the operation display mode, keep the [para] key
pressed for 2 s or longer.
>>
The unit then enters the parameter setting mode.
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(2) Press the [para] key several times.
>>
Display the parameter setting [I-1: Integral time].
rdy
man
ev1 ev2 ev3 ot1 ot2
para
mode
pv
sp
(3) Press the [
], or [
] key to change the set value in
[I-1].
Setting range: 0 to 9999s
>>
When no keys are pressed for 2 s or longer, the flashing of the numeric
value is stopped to set the currently displayed value.
(4) Press the [mode] key.
The display is returned to the operation display.
Handling Precautions
When [CtrL: Control method] is set at [0: ON/OFF control], [I-1] is not
displayed.