4-8
Chapter 4. BASIC OPERATION
Flow rate setup by external 3-way switching input (Advanced use)
When "2: Switching of SP No." is assigned at external 3-way switching function
C-09
in the function setup, three SP values (
SP-0
to
SP-2
) can be changed with
the external 3-way switching input as described in the table below.
External 3-way switching input state Selected SP
OPEN SP-0
0 V SP-1
5 V SP-2
Handling Precautions
When the SP No. is switched by the external 3-way switching input, you
cannot switch the SP No. using or keys, though you can switch the SP
value.