M2000 memory map by register address Page 19/30
MID_M2000_BA_MODBUS_02_1805
Register address
Register name
Register type
0x00C9
Port B: Packets received
UINT16
0x00CA
Port B: Packets sent
UINT16
0x00CB
Port B: Parity errors
UINT16
0x00CC
Port B: Framing errors
UINT16
0x00CD
Port B: Overrun errors
UINT16
0x00CE
Port B: Break detects
UINT16
0x00CF
T1 /T+ [m
3
]
FLOAT32
0x00D1
Reserved (to addr 0x00D2) FLOAT 64
UINT16 [2]
0x00D3
T1 /T+ [user units]
FLOAT32
0x00D5
Reserved (to addr 0x00D6) FLOAT 64
UINT16 [2]
0x00D7
T2 /T- [m
3
]
FLOAT32
0x00D9
Reserved (to addr 0x00DA) FLOAT 64
UINT16 [2]
0x00DB
T2 /T- [user units]
FLOAT32
0x00DD
Reserved (to addr 0x00DE) FLOAT 64
UINT16 [2]
0x00DF
T3 /TN [m
3
]
FLOAT32
0x00E1
Reserved (to addr 0x00E2) FLOAT 64
UINT16 [2]
0x00E3
T3 /TN [user units]
FLOAT32
0x00E5
Reserved (to addr 0x00E6) FLOAT 64
UINT16 [2]
0x00E7
T1 /T+ Rollover counter
UINT16
0x00E8
T2 /T- Rollover counter
UINT16
0x00E9
Flow velocity [m/s]
FLOAT32
0x00EB
Preset batch totalizer [m
3
]
FLOAT32
0x00ED
Flow rate [m
3
/s]
FLOAT32
0x00EF
Preset batch totalizer [user units]
FLOAT32
0x00F1
Flow rate [user units]
FLOAT32
0x00F3
Relative flow rate [%]
FLOAT32
0x00F5
Power up counter
UINT16
0x00F6
Detector error counter
UINT16
0x00F7
Empty pipe counter
UINT16
0x00F8
Full scale counter
UINT16
0x00F9
Totalizer overflow counter
UINT16
0x00FA
Reserved
UINT16
0x00FB
Reserved
UINT16
0x00FC
Pulse sync counter
UINT16