EasyManua.ls Logo

Bailey INFI 90 IMCOM03 - Dipshunt Assignments; Terminal Assignments

Bailey INFI 90 IMCOM03
77 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TERMINATION UNIT CONFIGURATION (NTCS02)
INTRODUCTION
A - 4 I-E96-207A
®
Terminal Assignments
Figure A-2 shows the termination assignment for the termina-
tion unit (TCS).
Table A-2. Dipshunt Assignments
DipShunt Assignment Fixed Block
*
Terminal Block
(TB)
Terminal Position
+-
XU1
XU2
XU3
Analog Input 1
Analog Input 2
Analog Input 3
201
202
203
1
2
3
10 9
10 9
10 9
XU4
XU5
XU6
Analog Input 4
Digital Input 1
Digital Input 2
204
221
222
4
2
2
10 9
43
21
XU7
XU8
Digital Input 3
Electric Drive SAC
(Analog Control Station)
Position Feedback
223 3 4 3
XU9 Analog Output 1
Analog Output 2
211
212
1
4
87
87
* Refer to Product Information E93-900-20, Function Code Reference Manual, for block details.
Figure A-2. NTCS02 Terminal Assignments
T00121A
1
2
3
4
5
6
7
8
9
10
ELECTRIC
DRIVE
ONLY
ELECTRIC
DRIVE
ONLY
TB4
RAISE 2
R/L COMMON 2
LOWER 2
M/A POWER 2
M/A SELECT 2
M/A COMMON 2
–AO2
+(XU9)
–AI4
+(XU4)
TB3
COMMON
+24 VDC
–DI3
+(XU7)
+
+
–AI3
+(XU3)
DO4
DO3
TB2
–DI2
+(XU8)
–DI1
+(XU5)
+
+
–AI2
+(XU2)
DO2
DO1
TB1
RAISE 1
R/L COMMON 1
LOWER 1
M/A POWER 1
M/A SELECT 1
M/A COMMON 1
–AO1
+(XU9)
–AI1
+(XU1)
NOTE: AI = ANALOG INPUT, AO = ANALOG OUTPUT, DI = DIGITAL INPUT, DO = DIGITAL OUTPUT,
M/A = MANUAL/AUTOMATIC, (XUn) = DIPSHUNT USED FOR I/O.