EasyManua.ls Logo

Baldor VS1MX - Page 36

Baldor VS1MX
68 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-8 Parameter Descriptions MN762
Number
Name
(Display Level)
Value Range, Description and Preset Value
P-35 Serial Comms address Range: Adr: 0 (disable) to 63
Preset: Adr: 1
Sets a unique drive address for communication network
Modbus enable / baudrate
select
Range: OP-buS, 9.6, 19.2, 38.4, 57.6, 115.2 kBPS
Preset: OP-buS
When set to OP-buS, MODBUS disabled. Setting a baudrate enables MODBUS
at that baudrate and disables OP-buS (Also called MXSTBus)
Trip enable / delay Range: 0 (no trip)
t 30, 100, 1000, 3000 (ms)
r 30, 100, 1000, 3000 (ms)
Preset: t3000 (3 second trip)
The time before a trip in the event of a communication loss can be set in
milliseconds.
Setting 0 disables the communications trip.
t indicates the drive will trip if time exceeded.
r indicates the drive will ramp to stop if time exceeded.
P-36 V/F Frequency Adjustment Range: 0 to P-03Hz
Preset: 0.0
Sets the frequency at which the adjustment voltage set in P-37 is applied.
P-37 V/F Voltage Adjustment Range: 0 to P-01V
Preset: 0
Sets the applied motor voltage at the frequency set in P-36.
P-38 User PI Proportional Gain Range: 0.1 - 30.0
Preset: 1.0
Increase the value for high inertia. Too large a value gives instability.
P-39 User PI Integral Time
Constant
Range: 0.0s - 30.0seconds
Preset: 1.0
Higher values gives slower, more damped response.
P-40 User PI Feedback Mode Range: 0 or 1
Preset: 0
0: Direct
1: Inverse (When set to 1, the bipolar analog input is used)
Sets the source for the PI control reference signal.
P-41 User PI Reference Select Range: 0 or 1
Preset: 0
0: Digital
1: Analog (The bipolar analog input is used)
Sets the source for the PI control reference signal.
Note: Parameter setting is ignored (irrelevant) when P-07 is set to 5 and P-08 is
set to 9.
P-42 User PI Digital Reference Range: 0 to 100.0%
Preset: 0.0
Sets the preset reference used when P-41 = 0.
Table 7-1 Parameter Descriptions Continued

Table of Contents

Related product manuals