Parameter Tables B-1MN762
Appendix B
Parameter Tables
B.1 Parameters Sorted by Parameter Number
Table B-1 Parameters Sorted by Parameter Number
Param
#
Access Parameter Name Description (Range)
Factory
Setting
User
Setting
P00 RO Read Only Parameters 1-20
P01 RW Motor Rated Volts 0, 20-250VAC or 0, 20-500VAC 0
P02 RW Motor Rated Current 25-100% CALC
P03 RW Motor Rated Frequency 25 to 500 Hz 60
P04 RW Motor Rated Speed 0 to 30000 RPM 0
P05 RW Minimum Output Speed 0.0 to P06 (max 500.0Hz) 0.0
P06 RW Maximum Output Speed P05 to 5*P03 (max 500Hz) 60.0
P07 RW Start/Stop Source
0- Terminal Strip
1- Keypad FWD
2- Keypad bi-directional
3- MODBUS with accel / decel ramps
4- MODBUS with accel / decel ramp adjustment
5- User PI with external FDBK
6- User PI control Analog Input
0
P08 RW Operating Mode 0-12 0
P09 RW Stop Mode
0: Ramp to stop
1: Coast to stop
2: Ramp to stop (fast stop)
0
P10 RW Accel Time 0 to 600 seconds 5.0
P11 RW Decel Time 0 to 600 seconds 5.0
P12 RW Preset Speed 1 -P06 to P06 0.0
P13 RW Preset Speed 2 -P06 to P06 0.0
P14 RW Preset Speed 3 -P06 to P06 0.0
P15 RW Preset Speed 4 -P06 to P06 0.0
P16 RW Speed Reference Scaling 0 to 500% 100.0
P17 RW
Analog Input Format
(Analog In 1)
0-10V, 0-20mA, 4-20mA, 20-4mA u 0-10
P18 RW Voltage Boost 0.0 to 20.0% CALC
P19 RW Energy Savings
0: Disabled
1: Enabled
0
P20 RO Trip Log Last Four Trips Stored
P21 RW PWM Frequency 4 to 32 kHz 16
P22 RW Relay Output
0: Drive enabled
1: Drive healthy
2: Motor at target speed
3: Drive tripped
4: Motor speed >= limit
5: Motor current >= limit
6: Motor speed < limit
7: Motor current < limit
1
P23 RW Display Speed Scale Factor Custom scaling factor used only if P-04 > 0 0.000