9424200996 30-5
BE1-11m Metering
Figure 30-5. Analog Metering, Frequency Screen
Differential
The differential value is calculated as shown in the following equations:
If 87 Mode = Phase Differential and Slope Mode = Maximum, then IOP A =
|

+

|
where: I

=


and I

=


Equation 30-1. IOP A Calculation when 87 Mode = Phase Differential
If 87 Mode = Flux Balance, then IOP A =
|
IA
|
Equation 30-2. IOP A Calculation when 87 Mode = Flux Balance
If 87 Mode = Phase Differential, then IR A = max
(
IRA
, IRA
)
Equation 30-3. IR A Calculation when 87 Mode = Phase Differential and Slope Mode = Maximum
If 87 Mode = Phase Differential and Slope Mode = Average, then IR A = avg
(
IRA
, IRA
)
Equation 30-4. IR A Calculation when 87 Mode = Phase Differential and Slope Mode = Average
Differential metering data is found in BESTCOMSPlus (Figure 30-6) and on the Metering > Analog
Metering > Differential screen of the front-panel display.