EasyManua.ls Logo

Basler BE1-11m - BestnetPlus

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 43-1
BE1-11m BESTnetPlus
43 • BESTnetPlus
BE1-11m Motor Protection Systems with an Ethernet port have a web page interface that can be used to
view BE1-11m status, real-time data, demand data, faults, sequence of events, and power quality. Refer
to the Communication chapter for information about configuring the BE1-11m to communicate through the
Ethernet port. Verify that Enable Web Pages is selected on the Settings, Communications, Ethernet
screen in the Settings Explorer of BESTCOMSPlus® or on the Settings > Communication > Ethernet
screen of the front-panel display. Using a web browser, enter the IP Address of your BE1-11m in the
address bar. The protection system’s IP address is found on the front-panel display under Settings >
Communication > Ethernet. Figure 43-1 shows an example for a BE1-11m with an IP address of
10.0.129.101.
Figure 43-1. Address Bar of Web Browser
Status Page
Figure 43-2 illustrates the Status (home) page. Device information, firmware version, breaker status,
lockout status, motor status, alarm status, targets, local inputs status, and local outputs status are shown
on this page. A green indicator lights to indicate an energized state for inputs and outputs.
Figure 43-2. Status Page (Home Page)
Real Time Data
Figure 43-3 illustrates the Real Time Data page. Values for currents, frequency, voltages, and power are
shown on this page.

Table of Contents

Related product manuals