9424200996 83-1
BE1-11m RTD Module
83 • RTD Module
The RTD (Resistance Temperature Detector) module is an optional remote device that provides RTD
inputs, analog inputs, and analog outputs for motor protection applications.
Features
RTD modules have the following features:
12 RTD Inputs
4 Analog Inputs
4 Analog Outputs
Secured Read/Write Access*
Reporting and Alarm Functions
Communications via Ethernet or RS-485
* The default password for uploading settings to the RTD module is “OEM in upper case letters.
Functional Description
A functional description of the RTD module’s inputs and outputs is provided below.
Analog Inputs
The RTD module provides four analog inputs that are user-selectable for 4 to 20 mAdc or 0 to 10 Vdc.
Each analog input has under/over thresholds that when exceeded, trip an analog input protection
element. RTD modules with firmware 1.01.01 and above limit measurements in relation to the 4 to 20
mAdc or 0 to 10 Vdc range. Firmware below 1.01.01 is not operational outside the ranges. The label text
of each analog input is customizable.
RTD Inputs
The RTD module provides 12 user-configurable RTD inputs for monitoring motor systems. Each RTD
input can be configured to protect against high or low temperature conditions. The label text of each RTD
input is customizable.
Analog Outputs
The RTD module provides four analog outputs that are user-selectable for 4 to 20 mAdc or 0 to 10 Vdc. A
wide selection of parameters including BE1-11m metered voltages and currents, analog inputs, and RTD
inputs can be configured as analog outputs. Refer to the Programmable Outputs, Remote Analog Outputs
screen in BESTCOMSPlus® for a full list of parameter selections.
Alarm Contact Functions
The RTD module provides form C (SPDT) alarm contacts that operate when an internal RTD module
failure exists. The contacts also operate when operating power is cycled.
Real-Time Status Functions
The RTD module is equipped with a multi-function LED with the following functions.
Slow Flashing - Communications established
Quick Flashing - Communications lost
Steady On - Power applied

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Basler BE1-11m and is the answer not in the manual?

Basler BE1-11m Specifications

General IconGeneral
BrandBasler
ModelBE1-11m
CategoryProtection Device
LanguageEnglish

Related product manuals