Basler BE1-11m - Ampere CT Continuous Rating; One Second Rating; For Other Current Levels, Use the Following Formula: I = (K;T); ½ Where T = Time in Seconds, K

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
80-8 9424200996
Specifications BE1-11m
Restraint Slope 1
Setting Range ........................................................... 5 to 100%
Restraint Slope 2
Setting Range ........................................................... 15 to 140%
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy.................................................................... ±0.5% or ±½ cycle, whichever is greater, plus trip
time for instantaneous response (0.0 setting)*
* Trip Time for 0.0 Delay Setting .............................. 1¼ cycles maximum for currents 5 times the pickup
setting. 1¾ cycles maximum for a current of 2
times pickup. Two cycles maximum for a current
of 1.05 times the pickup setting.
Restart Inhibit Protection
Restart Delay
Setting Range ........................................................... 0 to 7,200 min
Accuracy.................................................................... ±0.5% or ±3 cycles
Time Between Starts
Setting Range ........................................................... 0 to 7,200 min
Accuracy.................................................................... ±0.5% or ±3 cycles
Automatic Setting Group Characteristics
Number of Setting Groups ........................................ 4
Control Modes
Automatic .................................................................. Cold-Load Pickup, Dynamic Load or Unbalance
External ..................................................................... Discrete Input Logic, Binary Input Logic
Switch Threshold
Range ........................................................................ 0.1 to 25 A (5 A), 0.02 to 5 A (1 A)
Accuracy.................................................................... ±2% or ±0.05 A (5 A), ±2% or ±0.01 A (1 A)
Switch Time
Range ........................................................................ 0 to 60 min with 1 min increments where 0 =
disabled
Accuracy.................................................................... ±0.5% or ±2 s, whichever is greater
BESTlogicPlus
Update Rate .............................................................. ¼ cycle
General Specifications
AC Current Inputs
5 Ampere CT
Continuous Rating ..................................................... 20 A
One Second Rating ................................................... 400 A
For other current levels, use the formula: I= (K/t)
½
where t = time in seconds, K = 160,000.
Begins to Clip (Saturate) ........................................... 150 A
Burden ....................................................................... <10 m