EasyManua.ls Logo

Basler BE1-11m - Page 471

Basler BE1-11m
610 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9424200996 80-7
BE1-11m Specifications
81 - Frequency Protection
O/U
Pickup
Setting Range ........................................................... 15 to 110 Hz
Accuracy.................................................................... ±0.01 Hz
Dropout ...................................................................... 0.02 Hz ±0.01 Hz of the actual pickup value
Time Delay
Setting Range ........................................................... 0 to 600,000 ms
Accuracy.................................................................... ±0.5% or ±1 cycle, whichever is greater, plus 3
cycle recognition time for time delays < 50 ms
ROC
Pickup
Setting Range ........................................................... 0.2 to 20 Hz/sec (positive, negative, or either)
Accuracy.................................................................... ±2% or ±0.1 Hz/sec of the setting, whichever is
greater
Dropout ...................................................................... ±3% of the actual pickup value
Over/Underfrequency Inhibit
Setting Range ........................................................... 15 to 110 Hz
Increment .................................................................. 0.01 Hz
Accuracy.................................................................... ±0.01 Hz
Negative-Sequence Inhibit
Setting Range ........................................................... 0 to 99% of nominal voltage
Accuracy.................................................................... ±0.5% or ±1 V, whichever is greater
Time Delay
Setting Range ........................................................... 0 to 600,000 ms
Accuracy.................................................................... ±0.5% or ±1 cycle, whichever is greater, plus
recognition time*
* Recognition time = 2 cycles for 0.57 > pickup, 4 cycles for 0.24 > pickup, 8 cycles for 0.08 > pickup, 16
cycles at pickup
O/U/ROC Voltage Inhibit
Setting Range ........................................................... 15 to 250 V
Accuracy.................................................................... ±2% or ±1 V, whichever is greater
87 - Phase Current Differential Protection
Restrained Differential
5 Ampere CT Pickup Accuracy ................................. ±4% or ±75 mA, whichever is greater
1 Ampere CT Pickup Accuracy ................................. ±4% or ±25 mA, whichever is greater
Response Time ......................................................... <2 cycles at 5 times pickup
<3 cycles at 1.5 times pickup
TAP
5 Ampere CT Setting Range ..................................... 2.00 to 20.0 A
1 Ampere CT Setting Range ..................................... 0.40 to 4.00 A
Minimum Restraint Pickup (I
op
)
Setting Range ........................................................... 0.1 to 1.00 per unit
2
nd
Slope Pickup (I
res
)
Setting Range ........................................................... 0.1 to 20.0 per unit