60-10 9424200996
Auxiliary Overvoltage (59X) Test BE1-11m
† VA Low and High values are calculated as VA=3V0+150 V nominal.
Timing Verification (3V0 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (V1 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98% ±1%
Step
Pickup
Setting
Low
Actual
Pickup
High
Low*
Actual
Dropout
High*
Pass/Fail
V1
VA
V1
VA
V1
VA
V1
VA
V1
VA
6
82.0
246.0
80.3
240.9
83.6
250.8
82.8
248.4
84.4
253.2
P / F
7
42.0
126.0
41.0
123.0
43.0
129.0
42.4
127.2
43.2
129.6
P / F
7
25.0
75.0
24.0
72.0
26.0
78.0
25.2
75.6
25.7
77.1
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (V1 Mode)
Time Delay Range = 50 to 600,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,968 ms
2,032 ms
P / F
5
5,000 ms
4,968 ms
5,032 ms
P / F
5
10,000 ms
9,950 ms
10,050 ms
P / F
Pickup Verification (V2 Mode)
Pickup Setting Range = 1 to 150 V
Pickup Accuracy = ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio = 98% ±1%
Step
Pickup
Setting
Low
Actual
Pickup
High
Low*
Actual
Dropout
High*
Pass/Fail
V1
VA
V1
VA
V1
VA
V1
VA
V1
VA
6
82.0
246.0
80.3
240.9
83.6
250.8
82.8
248.4
84.4
253.2
P / F
7
42.0
126.0
41.0
123.0
43.0
129.0
42.4
127.2
43.2
129.6
P / F
7
25.0
75.0
24.0
72.0
26.0
78.0
25.2
75.6
25.7
77.1
P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (V2 Mode)
Time Delay Range = 50 to 600,000 ms