9424200996 65-13
BE1-11m Inverse Overcurrent (51) Test
Dropout should occur between 93-99% of the actual pickup value.
Step
Actual
Pickup
Actual
Dropout
Pass/Fail
6
1.50 0.42
1.26 0.57 1.71 0.46 1.38 0.49 1.47 P / F
7
15.00 4.85
14.55 5.15 15.45 4.65 13.95
4.95 14.85 P / F
7
27.00 8.73
26.19 9.27 27.81 8.37 25.11
8.91 26.73 P / F
6
0.30 0.08
0.24 0.11 0.33 0.093 0.279
0.099 0.297 P / F
7
3.00 0.97
2.91 1.03 3.09 0.93 2.79 0.99 2.97 P / F
7
5.40 1.74
5.22 1.85 5.55 1.67 5.01 1.78 5.34 P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (I2 Mode, 5A Sensing)
Time Dial Range = 0.0 to 9.9
Timing Accuracy = ±5% or ±1½ cycles, whichever is greater
Timing Verification (I2 Mode, 1A Sensing)
Time Dial Range = 0.0 to 9.9
Timing Accuracy = ±5% or ±1½ cycles, whichever is greater