BE1-11m Thermal Curve (49TC) Test
Table 70-2. Operational Settings, RTD Biasing
General Settings, Display Units
Sets System Units to
Metric (°C)
System Parameters, Motor
Configuration
Sets Nominal Frequency
to 60 Hz
Secondary Phase
Current CT1
System Parameters, Motor
Configuration
Sets Secondary Phase
Current CT1 to 5 A
System Parameters, Motor
Configuration
System Parameters, Motor
Configuration
System Parameters, Sensing
Transformers
Sets Phase CT Ratio
CT1 to 1
System Parameters, Remote
Module Communications
System Parameters, Remote
Module Communications
Selects Ethernet or
RS485 Communication
Module ID
Remote
System Parameters, Remote
Module Communications
Module ID
Platinum
Programmable Inputs, Remote
RTD, RTD Type Selection
Platinum Resistor for
Programmable Inputs, Remote
RTD, RTD Block Configuration
Enables RTD 1 for
Remote Module 1
Protection, Thermal, RTD Bias
Curve
Sets Point 1 Temp to
40°C
Protection, Thermal, RTD Bias
Curve
Protection, Thermal, RTD Bias
Curve
Sets Point 2 Temp to
250°C
Protection, Thermal, RTD Bias
Curve
Protection, Thermal, Thermal
Curve (49TC)
Selects Standard Curve
mode
Protection, Thermal, Thermal
Curve (49TC)
Protection, Thermal, Thermal
Curve (49TC)
Selects RTD Group 1
Block
Protection, Thermal, Thermal
Curve (49TC)
Sets Standard Curve
Time Dial to 10
Protection, Thermal, Thermal
Curve (49TC)
Protection, Thermal, Thermal
Curve (49TC)
Sets Overload pickup to
1
Max Emergency
Thermal Capacity
Protection, Thermal, Thermal
Curve (49TC)
Sets Max Emergency
Thermal Capacity to 0%