BE1-11m Thermal Curve (49TC) Test
Table 70-2. Operational Settings, RTD Biasing
Setting
Value
BESTCOMSPlus Screen
Description
System Units
Metric
General Settings, Display Units
Sets System Units to
Metric (°C)
Frequency
60
System Parameters, Motor
Configuration
Sets Nominal Frequency
to 60 Hz
Secondary Phase
Current CT1
5
System Parameters, Motor
Configuration
Sets Secondary Phase
Current CT1 to 5 A
Full Load Amps
2
System Parameters, Motor
Configuration
Sets Full Load Amps to 2
Service Factor
1
System Parameters, Motor
Configuration
Sets Service Factor to 1
Phase CT Ratio CT1
1
System Parameters, Sensing
Transformers
Sets Phase CT Ratio
CT1 to 1
RTD1 Status
Enabled
System Parameters, Remote
Module Communications
Enables Remote Module
RTD1
Communication Type
Ethernet or
RS485
System Parameters, Remote
Module Communications
Selects Ethernet or
RS485 Communication
RTD1 Remote
Module ID
Set per
Remote
Module ID
System Parameters, Remote
Module Communications
Defines the Remote
Module ID
RTD #1 Type
100
Platinum
Programmable Inputs, Remote
RTD, RTD Type Selection
Simulates a 100
Platinum Resistor for
RTD #1
RTD 1
Enabled
Programmable Inputs, Remote
RTD, RTD Block Configuration
Enables RTD 1 for
Remote Module 1
Point 1 Temp °C
40
Protection, Thermal, RTD Bias
Curve
Sets Point 1 Temp to
40°C
Point 1 %TC
10
Protection, Thermal, RTD Bias
Curve
Sets Point 1 to 10% TC
Point 2 Temp °C
250
Protection, Thermal, RTD Bias
Curve
Sets Point 2 Temp to
250°C
Point 2 %TC
80
Protection, Thermal, RTD Bias
Curve
Sets Point 2 to 80% TC
Element Mode
Standard
Curve
Protection, Thermal, Thermal
Curve (49TC)
Selects Standard Curve
mode
RTD Biasing
Enabled
Protection, Thermal, Thermal
Curve (49TC)
Enables RTD Biasing
RTD Source
RTD Group 1
Protection, Thermal, Thermal
Curve (49TC)
Selects RTD Group 1
Block
Standard Curve Time
Dial
10
Protection, Thermal, Thermal
Curve (49TC)
Sets Standard Curve
Time Dial to 10
K
0
Protection, Thermal, Thermal
Curve (49TC)
Sets K to 0
Overload
1
Protection, Thermal, Thermal
Curve (49TC)
Sets Overload pickup to
1
Max Emergency
Thermal Capacity
0
Protection, Thermal, Thermal
Curve (49TC)
Sets Max Emergency
Thermal Capacity to 0%