BE1-11m Thermal Curve (49TC) Test
Table 70-3. Operational Settings, User Curve
Setting
Value
BESTCOMSPlus Screen
Description
Nominal Frequency
60
System Parameters, Motor
Configuration
Sets Nominal Frequency
to 60 Hz
Nominal Secondary
Phase Voltage
69.3
System Parameters, Motor
Configuration
Sets Nominal Secondary
Phase Voltage to 69.3 V
Nominal Secondary
Phase Current CT1
5
System Parameters, Motor
Configuration
Sets Secondary Phase
Current CT1 to 5 A
Full Load Amps
2
System Parameters, Motor
Configuration
Sets Full Load Amps to 2
Service Factor
1
System Parameters, Motor
Configuration
Sets Service Factor to 1
Phase CT Ratio CT1
1
System Parameters, Sensing
Transformers
Sets Phase CT Ratio CT1
to 1
Phase VT Ratio
1
System Parameters, Sensing
Transformers
Sets Phase CT Ratio CT1
to 1
Phase VT Connection
3W-D
System Parameters, Sensing
Transformers
Selects 3W-D Phase VT
Connection
Element Mode
User
Curve
Protection, Thermal, Thermal Curve
(49TC)
Selects User Curve mode
RTD Biasing
Disabled
Protection, Thermal, Thermal Curve
(49TC)
Disables RTD Biasing
Standard Curve Time
Dial
10
Protection, Thermal, Thermal Curve
(49TC)
Sets Standard Curve
Time Dial to 10
K
0
Protection, Thermal, Thermal Curve
(49TC)
Sets K to 0
Overload
1
Protection, Thermal, Thermal Curve
(49TC)
Sets Overload pickup to 1
Max Emergency
Thermal Capacity
0
Protection, Thermal, Thermal Curve
(49TC)
Sets Max Emergency
Thermal Capacity to 0%
Running Cool Time
Constant
1
Protection, Thermal, Thermal Curve
(49TC)
Sets Running Cool Time
Constant to 1 minute
Stopped Cool Time
Constant
1
Protection, Thermal, Thermal Curve
(49TC)
Sets Stopped Cool Time
Constant to 1 minute
Hot Safe Stall Time
1
Protection, Thermal, Thermal Curve
(49TC)
Sets Hot Safe Stall Time
to 1 second
Cold Safe Stall Time
1
Protection, Thermal, Thermal Curve
(49TC)
Sets Cold Safe Stall Time
to 1 second
Curve 1 Voltage %
90
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1 Voltage to
90%
Curve 1 Point 1 xPU
1.3
Protection, Thermal, 49TC User
Table Curve, Overload Curve
Sets Curve 1, Point 1 xPU
to 1.3
Curve 1 Point 1 Time
20
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1, Point 1
Time to 20 seconds.
Curve 1 Point 2 xPU
10
Protection, Thermal, 49TC User
Table Curve, Overload Curve
Sets Curve 1, Point 1 xPU
to 10
Curve 1 Point 2 Time
0.1
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1, Point 1
Time to 100 milliseconds