9424200996 70-7
BE1-11m Thermal Curve (49TC) Test
Table 70-3. Operational Settings, User Curve
System Parameters, Motor
Configuration
Sets Nominal Frequency
to 60 Hz
Nominal Secondary
Phase Voltage
System Parameters, Motor
Configuration
Sets Nominal Secondary
Phase Voltage to 69.3 V
Nominal Secondary
Phase Current CT1
System Parameters, Motor
Configuration
Sets Secondary Phase
Current CT1 to 5 A
System Parameters, Motor
Configuration
System Parameters, Motor
Configuration
System Parameters, Sensing
Transformers
Sets Phase CT Ratio CT1
to 1
System Parameters, Sensing
Transformers
Sets Phase CT Ratio CT1
to 1
System Parameters, Sensing
Transformers
Selects 3W-D Phase VT
Connection
Protection, Thermal, Thermal Curve
(49TC)
Protection, Thermal, Thermal Curve
(49TC)
Protection, Thermal, Thermal Curve
(49TC)
Sets Standard Curve
Time Dial to 10
Protection, Thermal, Thermal Curve
(49TC)
Protection, Thermal, Thermal Curve
(49TC)
Sets Overload pickup to 1
Max Emergency
Thermal Capacity
Protection, Thermal, Thermal Curve
(49TC)
Sets Max Emergency
Thermal Capacity to 0%
Running Cool Time
Constant
Protection, Thermal, Thermal Curve
(49TC)
Sets Running Cool Time
Constant to 1 minute
Stopped Cool Time
Constant
Protection, Thermal, Thermal Curve
(49TC)
Sets Stopped Cool Time
Constant to 1 minute
Protection, Thermal, Thermal Curve
(49TC)
Sets Hot Safe Stall Time
to 1 second
Protection, Thermal, Thermal Curve
(49TC)
Sets Cold Safe Stall Time
to 1 second
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1 Voltage to
90%
Protection, Thermal, 49TC User
Table Curve, Overload Curve
Sets Curve 1, Point 1 xPU
to 1.3
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1, Point 1
Time to 20 seconds.
Protection, Thermal, 49TC User
Table Curve, Overload Curve
Sets Curve 1, Point 1 xPU
to 10
Protection, Thermal, 49TC User
Table Curve, Voltage Configuration
Sets Curve 1, Point 1
Time to 100 milliseconds