9424200996 70-9
BE1-11m Thermal Curve (49TC) Test
Timing Verification (Standard Curve with Emergency Start)
Time Dial Range = 1 to 20
Timing Accuracy = ±5% or ±2½ cycles, whichever is greater
Timing Verification (Standard Curve with RTD Biasing)
Time Dial Range = 1 to 20
Timing Accuracy = ±5% or ±2½ cycles, whichever is greater