BE1-11m Thermal Curve (49TC) Test
Timing Verification (Standard Curve with Emergency Start)
Time Dial Range = 1 to 20
Timing Accuracy = ±5% or ±cycles, whichever is greater
Step
Time Dial
Applied Current
Low
Actual Timing
High
Pass/Fail
17
10
10 A
68.818 sec
76.062 sec
P / F
Timing Verification (Standard Curve with RTD Biasing)
Time Dial Range = 1 to 20
Timing Accuracy = ±5% or ±cycles, whichever is greater
Step
Time Dial
Applied Current
Low
Actual Timing
High
Pass/Fail
22
10
10 A
29.934 sec
33.085 sec
P / F