75-8 9424200996
Logic Timers (62) Test BE1-11m
Figure 75-7. BESTlogicPlus Settings (Latched Mode)
Note
The 43-1 switch action is performed twice in this test. The 43-2 switch
action is performed once. Follow the timing sequence to illustrate time
mode action. The time delay settings can be increased if difficulty is
encountered with repeating the 43-1 and 43-2 switch actions.
Step 5: Using the front-panel display, navigate to Metering > Control > Virtual Switches screen.
Highlight the first switch (43-1) and press the Right key on the front panel to enter the 43-1
control screen. Use the Edit key to login. Highlight Operate and then press the Edit key to
change the state of the 43-1. Using the Up/Down keys select PUL and then press the Edit key.
Step 6: Repeat step 5 within 30 seconds.
Step 7: Wait at least 30 seconds (total elapsed time) before beginning step 8.
Step 8: Using the front-panel display, navigate to Metering > Control > Virtual Switches. Highlight the
second switch (43-2) and press the Right key on the front panel to enter the 43-2 control
screen. Use the Edit key to login. Highlight Operate and then press the Edit key to change the
state of the 43-2. Using the Up/Down keys select PUL and then press the Edit key.
Step 9: Use the Metering Explorer in BESTCOMSPlus to open the Reports, Sequence of Events
screen. Verify that the 62-1 timer output remained false after the first 43-1 switch action (ON),
the 62-1 timer output went true 30 seconds after 43-1 switch action (ON), and 62-1 timer output
returned to a false state with the 43-2 switch action (ON). Figure 75-8 illustrates the timing
relationship of the 43-1/43-2 switches and 62-1 timer.
Step 10: (Optional.) Repeat steps 1 through 9 for 62-1, 62-2, 62-3, 62-4, 62-5, 62-6, 62-7, and 62-8.
Step 11: (Optional.) Repeat steps 1 through 10 for Settings Group 1, 2, and 3.