9424200996 80-13
BE1-11m Specifications
Panel Display
64 by 128 dot pixels LCD with LED backlight.
Operating Temperature ............................................. 40 to 158°F (40 to 70°C). Display contrast
adjustment may be impaired below F (20°C).
Temperature
Operating Temperature Range ................................. 40 to 158°F (40 to 70°C)*
Storage Temperature Range .................................... 40 to 158°F (40 to 70°C)
* Display is inoperative below F (20°C)
Isolation
Meets IEC 255-5 and exceeds IEEE C37.90 one minute dielectric test as follows:
All Circuits to Ground* .............................................. 2,000 Vac or 2,828 Vdc
Input Circuits to Output Circuits ................................ 2,000 Vac or 2,828 Vdc
Communication Ports to Ground ............................... 700 Vdc for one minute
* Excludes communication ports.
Standards
IEC Standards:
IEC 60068-1 – Environmental Testing Part 1: General and Guidance. Temperature Test
IEC 60068-2-1 – Basic Environmental Testing Procedures, Part 2: Tests - Test Ad: Cold (Type
Test)
IEC 60068-2-2 – Basic Environmental Testing Procedures, Part 2: Tests - Test Bd: Dry Heat
(Type Test)
IEC 60068-2-28Environmental Testing Part 2: Testing-Guidance for Damp Heat Tests
IEC 60255-4 – Single Input Energizing Quantity Measuring Relays with Dependent Specified
Time
IEC 60255-5 – Electrical Insulation Tests for Electrical Relays. Dielectric Test and Impulse Test
IEC 60255-6 – Electrical Relays - Measuring Relays and Protection Equipment
IEC 60255-21-1 – Vibration, Shock, Bump, and Seismic Tests on Measuring Relays and
Protective Equipment (Section 1 - Vibration Test - Sinusoidal). Class 1
IEC 60255-21-2 – Vibration, Shock, Bump, and Seismic Tests on Measuring Relays and
Protective Equipment (Section 2 - Shock and Bump Test - Sinusoidal). Class 1
IEEE Standards:
IEEE Std C37.90.1-2002 IEEE Standard Surge Withstand Capability (SWC) Tests for Relays
and Relay Systems Associated with Electric Power Apparatus
IEEE Std C37.90.2-2004 IEEE Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
IEEE Std C37.90.3-2001 IEEE Standard Electrostatic Discharge Test for Protective Relays
CE Compliance
This product has been evaluated and complies with the relevant essential requirements set forth by the
EU legislation.
EC Directives:
LVD 2014/35/EU
EMC 2014/30/EU
RoHS 2 2011/65/EU