9424200996 81-3
BE1-11m Specifications - 25 Hz Operation
37 - Instantaneous Undercurrent Protection
Pickup
5 Ampere CT Setting Range ..................................... 0.5 to 100 A
1 Ampere CT Setting Range ..................................... 0.1 to 20 A
Reset ......................................................................... 101-107% of the actual pickup value
Accuracy
5 Ampere CT ............................................................. ±4% or ±50 mA, whichever is greater
1 Ampere CT ............................................................. ±4% or ±10 mA, whichever is greater
Inhibit Level
5 Ampere CT Setting Range ..................................... 0.5 to 100 A
1 Ampere CT Setting Range ..................................... 0.1 to 20 A
Reset ......................................................................... 101-107% of the actual pickup value
Accuracy
5 Ampere CT ............................................................. ±4% or ±50 mA, whichever is greater
1 Ampere CT ............................................................. ±4% or ±10 mA, whichever is greater
Time Delay
Setting Range ........................................................... 0 to 60,000 ms
Accuracy.................................................................... ±1.5% or 4 cycles, whichever is greater
40Q - Loss of Excitation Protection - Reverse var Based
Pickup
5 Ampere CT Setting Range ..................................... 1 to 6,000 var
1 Ampere CT Setting Range ..................................... 1 to 1,200 var
Accuracy.................................................................... ±4% or ±4 var, whichever is greater
Dropout ...................................................................... 93 to 99% of the actual pickup value
Time Delay
Setting Range ........................................................... 1 to 600,000 ms
Accuracy.................................................................... ±1.5 or ±4 cycles, whichever is greater
46 - Negative-Sequence Current Protection
Negative-sequence current protection is available when a 50 or 51 element is configured in I2 mode.
Refer to Instantaneous Overcurrent or Inverse Overcurrent for operational specifications.
47 - Negative-Sequence Voltage Protection
Negative-sequence voltage protection is available when a 59X element is configured in V2 mode. Refer
to Auxiliary Overvoltage for operational specifications.
48 - Incomplete Sequence Protection
Time Interval Range .................................................. 0 to 7,200 s
Accuracy.................................................................... ±1.5% or ± 4 cycles, whichever is greater
49RTD - Resistance Temperature Device Protection (Optional)
Pickup
Setting Range ........................................................... 32 to 482°F (0 to 250°C)
Accuracy.................................................................... ±2% or ±3.6°F (±C), whichever is greater
Reset/Pickup Ratio .................................................... 105% / 95% ±1% (over / under) or 41°F (5°C)
minimum