Specifications - 25 Hz Operation BE1-11m
59P - Phase Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 300 V
Accuracy.................................................................... ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98% ±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy.................................................................... ±1.5% or ± 2 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy.................................................................... ±8% or ±4 cycles, whichever is greater
59X - Auxiliary Overvoltage Protection
Pickup
Setting Range ........................................................... 1 to 150 V
Accuracy.................................................................... ±2% or ±1 V, whichever is greater
Dropout/Pickup Ratio ................................................ 98% ±1%
Timing Mode
Definite Timing
Setting Range ........................................................... 50 to 600,000 ms
Accuracy.................................................................... ±1.5% or ± 4 cycles, whichever is greater
Inverse Timing
Setting Range ........................................................... 0 to 9.9
Accuracy.................................................................... ±8% or ±4 cycles, whichever is greater
60FL - Fuse Loss
Time Delay ................................................................ Fixed at 50 ms
62 - Logic Timers
Modes ........................................................................ Pickup/Dropout, One-Shot/Non-Retriggerable,
One-Shot/Retriggerable, Oscillator, Integrating
Timer, Latched
Setting Range ........................................................... 0 to 9,999,000 ms
Accuracy.................................................................... ±0.5% or ±12 ms, whichever is greater
66 - Starts per Time Interval Protection
Time Interval
Setting Range ........................................................... 1 to 1,440 min
Accuracy.................................................................... ±0.5%
Number of Starts
Setting Range ........................................................... 1 to 100