BE1-11m Settings Calculation Examples
Figure 84-32. Synchronous Motor V Curves
General Settings
Display Units
Settings in this example are in metric and in secondary units, based upon multiples of FLA (Full Load
Amps) and phase-to-phase voltages, unless otherwise specified. Phase-to-phase voltages are configured
during phase VT setup.
Use the Settings Explorer in BESTCOMSPlus to navigate to the General Settings, Display Units screen.
Select Metric for System Units and Primary Units for Settings Display Modes, Thresholds. Refer to Figure
84-33.