Compatibility list
Operation Manual Safety Module for b maXX 5000 BM5-O-SAF-000/-001
Document no.: 5.09013.07 Baumüller Nürnberg GmbH
38
of 114
8.2
fixed SS1 time of 200 ms the drive is switched off by a safe pulse inhibit. After that the
module is in the STO state (safe torque off).
Safe Stop 1 (SS1) with time
control:
m When using the safety function SS1 the control of the power output stage is safely
i
nterrupted after a delay time of 200 ms. The drive can be braked to a stands
till by the
drive control within the SS1 time if appropriate parameterizations were made in the
controller (see Working Principle ZSAF-001-001-xxx– on page 40).
m The safety function SS1 corresponds to Stop Category 1 of EN 60204-1.
8.2 Compatibility list
8.2.1 Compatibility list SAF-001-000-xxx
The Safety Module (SAF-001-000-xxx) can only be operated in combination with
converters of the type b maXX 5000 released by the company Baumüller Nürnberg
GmbH.
If the converter was previously equipped with a module with a higher safety level
(
SAF-002/003), the parameter storage of the converter must be reset with the Reset-
Module.
8.2.2 Compatibility list SAF-001-001-xxx
The Safety Module (SAF-001-001-xxx) with automatic restart can only be operated in
combination with converters of the type b maXX 5000 with firmware version V01.10.02 or
h
igher by the company Baumüller Nürnberg GmbH. A firmware version V01.14.00 or
higher must be used for the Safety Module with SS1 function (SAF-001-001-001).
If the converter was previously equipped with a module with a higher safety level
(
SAF-001 without automatic restart, SAF-002 or SAF-003), the parameter storage of the
converter must be reset with the Reset-Module or with the reset command (see
ZOpe
ration mode of the reset command– on page 65).
If the converter was previously equipped with a module which includes a STO function
(
SAF-001-000-xxx, SAF-001-001-000) and is equipped with the module STO 001-001-
001 (SS1 function), the safety level of the converter must be reset to zero by the Reset
module or by the Reset command (see ZOpe
ration mode of the reset command– on
page 65).
WARNING!
A converter b maXX 5000 with a firmware version V01.14
.00 or higher must be used
for the Safety Module with SS1 function (SAF-001-001-001).