EasyManua.ls Logo

Baxi ECO5 BLUE - Boiler Parameter Visualisation; Using the INFO Function for Diagnostics

Baxi ECO5 BLUE
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7729106 (02-05/19) 30
INSTALLER Section (en)
11.2 REPLACING THE GAS VALVE
When replacing the gas valve, perform the following operations:
switch o󰀨 the boiler;
close the gas inlet valve;
replace the gas valve;
open the gas inlet valve and make sure there are no gas leaks;
perform the operations described in points 3 of the GAS CONVERSION section.
11.3 GAS VALVE CALIBRATION
To calibrate the gas valve, perform the operations described in points 3 of the GAS CONVERSION section.
11.4 REPLACING THE ELECTRONIC BOARD
When replacing the electronic board, perform the following operations:
disconnect the boiler from the mains power supply.
close the gas inlet valve;
remove the front panel of the boiler;
replace the electronic board;
power the boiler;
“the display shows “E98”;
set parameters F01, F02, F03 and F12 as described in the SETTING PARAMETERS section according to the boiler model
indicated on the data label.
11.5 REPLACING THE ELECTRONIC BOARD + GAS VALVE
When replacing the electronic board and the gas valve at the same time, perform the following operations:
disconnect the boiler from the mains power supply.
close the gas inlet valve;
remove the front panel of the boiler;
replace the electronic board;
replace the gas valve;
open the gas inlet valve and make sure there are no gas leaks;
power the boiler;
“the display shows “E98”;
set parameters F01, F02, F03 and F12 as described in the SETTING PARAMETERS section according to the boiler model
indicated on the data label.
perform the operations described in points 3 of the GAS CONVERSION section.
12. VISUALISATION OF PARAMETERS ON THE DISPLAY ("INFO" FUNCTION)
Press for at least 6 seconds to display information concerning boiler operation.
When the “INFO” function is enabled, the message A00” alternating with the boiler delivery temperature, is shown on the
display:
CG_1808
Press buttons to display the following information:
A00: current heating delivery temperature (°C);
A01: current DHW temperature (°C);
A02: current external temperature (°C) (with external sensor connected);
A03: current fumes temperature (°C);
A04: instantaneous (%) value of the gas valve control signal;
A05: power range (%) (MAX CH);
A06: heating setpoint temperature (°C);
A07: DHW temperature setpoint (°C);
A08: last error that occurred in the boiler;
A09: not used;
A10: not used.
This function remains active for 3 minutes. It is possible to interrupt the “INFO” function in advance by pressing or turning o󰀨
the power to the boiler.

Table of Contents

Related product manuals