13. PARAMETER SETTINGS
To set the boiler parameters, press and together and hold down for at least 6 seconds. When the function is activated, the
display shows “F01” alternated with the value of the parameter.
Edit parameters
• To scroll the parameters press ;
• Press
buttons to change the single parameter value;
• Press
to save changes, the display shows “MEM”;
• Press
to leave the function without saving, the display shows "ESC".
ALL MODIFIED PARAMETERS SHOULD BE NOTED DOWN IN THE TABLE AT THE END OF THIS MANUAL.
Parameter Description of parameters Factory settings
F01 Boiler type: 010=airtight chamber - 020=atmospheric chamber 020
F02 Gas used: 000=NATURAL GAS - 001=LPG 000 - 001
F03
Hydraulic system
000 = instantaneous appliance
003 = appliance with external storage boiler
004 = heating only appliance
000
F04 - F05
Setting programmable relays 1 and 2 (See SERVICE instructions)
000=no associated function
000
F06
Maximum heating setpoint setting (°C)
000=85°C (Burner goes out at 90 °C)
001=45°C (Burner goes out at 50 °C)
000
F07 DHW inlet priority conguration 000
F08 CH max. output (0-100%) 100
F09 DHW max. output (0-100%) 100
F10 CH and DHW min. heat output (0-100%) 000
F11
Delay prior to new ignition in CH mode
000=10 seconds - 001...010 = 1...10 minutes
003
F12 Identication of boiler model 007
F13
Pump overrun time in heating mode
000=10 seconds - 001...240 = 1...240 minutes
003
F14 Test of correct DHW probe position: 000=Disabled - 001=Always enabled 000
F15 Factory setting 000
F16
Anti-legionellosis function
000 = Disabled - 055…067 = Enabled (setpoint 55…67°C)
000
F17 Hydraulic pressure switch conguration 001
F18 Release parameters for SERVICE 000