INSTALLER Section (en)
7729106 (02-05/19)
CODE
DISPLAYED
FAULT POSSIBLE REASON SERVICE ACTION
E35 Parasite ame (ame
error).
• The electronic board is not
earthed.
• Flame sensing electrode faulty or
incorrectly positioned.
• Electronic board faulty.
• Check the continuity of the earth connections between
the electronic board (X4 connector) and the power
supply terminal block.
• Check the ame sensing electrode is in good
condition and correctly positioned (see the
POSITIONING THE IGNITION AND FLAME-
SENSING ELECTRODE section).
E98 Electronic board
parameters incorrectly
congured
• The electronic board has been
replaced and not yet calibrated
for the boiler model.
• Parameters F03 and F12 have
not been set or have been
incorrectly set.
• Set parameters F03 and F12 with the values indicated
in the table in the SETTING PARAMETERS section
according to the boiler model indicated on the rating
plate.
“St”
ashing
Defrosting function
enabled. The boiler does
not turn on the burner
and does not meet the
heat demands, or runs at
reduced power.
• Primary circuit frozen
• CH ow NTC probe faulty.
• Electronic board faulty.
• Defrost the boiler making sure that the appliance is not
supplied with power. Next, start up the burner (the “St”
code disappears after the burner has been running for
a few minutes).
• Check the CH ow NTC probe (*).
Flow
temperature
<2°C ashing
Defrosting function
enabled. The boiler does
not turn on the burner and
does not meet the heat
demands.
• Primary circuit frozen
• CH ow NTC probe faulty.
• Electronic board faulty.
• Defrost the boiler making sure that the appliance is not
supplied with power. Next, start up the burner (the “St”
code disappears after the burner has been running for
a few minutes).
• Check the CH ow NTC probe (*).
CH = central heating
DHW = domestic hot water
(*) DHW NTC and CH delivery probe: cold resistance value: approximately 10 kΩ @ 25° C (resistance decreases as temperature rises).