BA series pumps
1401 Pump unit with diesel drive
8.15
All diesel fuels sold as fuel and complying with the following minimum specification can be used:
EN 590 or
BS 2869 A1 / A2 or
ASTM D 975 - 1D / 2D
If the fuel tank is not mounted on top of the engine, or
is at a lower level, operate the lever on the fuel feed
pump until fuel is heard to flow back to the tank
through the return line.
At temperatures below 0 °C, winter-grade fuel should
be used or parafin added to the fuel well in advance.
Starting the engine
WARNING
Do not run the engine in closed or badly ventilated rooms – danger of poisoning!
WARNING
Before the engine is started, always make sure that nobody is in the danger area
(moving parts on engine or machinery) and that all safety guards are in place.
Renew tubular grip if broken, worn drive pin etc.
Lowest ambient
temperature when
starting, in ºC
Paraffin content for:
Summer fuel Winter fuel
0
-10
-15
-20
up to
up to
up to
up to
-10
-15
-20
-30
20%
30%
50%
-
-
-
20%
50%