Operation
EL6910 89Version: 1.4.1
Fig.121: Selecting the process data size and the process data
The process data can be adjusted to user requirements by selecting the Edit button in the dialog Configure I/
O element(s).
Fig.122: Selection of the process data
The safety address together with the CRC must be entered on the TwinSAFE SC slave side. This is done via
the CoE objects 0x8010:01 and 0x8010:02 of the corresponding TwinSAFE SC component. The address set
here must also be set in the alias device as FSoE address under the Linking tab.
Under the object 0x80n0:02 Connection Mode the CRC to be used is selected or a free CRC is entered. A
total of 8 CRCs are available. A free CRC must start with 0x00ff in the high word.
Fig.123: CoE objects 0x8010:01 and 0x8010:02