Questions and Answers

  • J
    Joseph BatesAug 14, 2025
    Why is I/O LED flashing red on BeiJer I/O Systems?
    • J
      Jennifer LopezAug 14, 2025
      The I/O LED might flash red on BeiJer I/O Systems due to a failure in configuration baud rate, initialization I/O, or the NA series noticing an unidentified expansion module ID. You should check the communication cable with the Master and the power for the master. Also, use an expansion slot of up to 63 and ensure the total I/O size is not excessive. Finally, check the status of the expansion module.
  • W
    William GloverAug 17, 2025
    What to do if all LED turns off on BeiJer I/O Systems?
    • T
      Timothy BenjaminAug 18, 2025
      If all LEDs turn off on your BeiJer I/O Systems, first check the main power cable. If the power cable is fine, it could be that the system power is not supplied, in which case you should contact the sales team and send the module for repair.
  • R
    Richard CollinsAug 21, 2025
    What to do if RUN LED flashed red on BeiJer I/O Systems?
    • C
      Carl WatkinsAug 21, 2025
      If the RUN LED flashes red on your BeiJer I/O Systems, the module configuration might have failed. To resolve this, check that the module hardware and software configurations are the same.
  • D
    Dawn SandersAug 25, 2025
    What to do if I/O LED is red on BeiJer I/O Systems?
    • J
      James MoraAug 25, 2025
      If the I/O LED is red on your BeiJer I/O Systems, it indicates a failure in exchanging I/O data. You should check the status of the expansion I/O connection.
  • M
    Mackenzie HuangAug 28, 2025
    How to fix MOD LED flashes red on BeiJer I/O Systems?
    • A
      Andrea FordAug 28, 2025
      If the MOD LED flashes red on your BeiJer I/O Systems, it could be due to an excess of expansion slots, an excess of I/O size, a wrong I/O composition, or an EEPROM checksum error. To fix this, use an expansion slot of up to 63, ensure that the total I/O size is not excessive, and check the composition of the I/O Module.
  • R
    Ryan TaylorAug 30, 2025
    Why is RUN LED flashing green on BeiJer I/O Systems?
    • D
      Denise MeyerAug 31, 2025
      The RUN LED might be flashing green on your BeiJer I/O Systems because the PLC program has stopped. Check that the toggle switch is up.
  • W
    whitewilliamSep 3, 2025
    What to do if I/O LED turns off on BeiJer I/O Systems?
    • S
      shawrobertSep 3, 2025
      If the I/O LED turns off on your BeiJer I/O Systems, it could be due to a failure of realization expansion Module or the absence of an expansion Module. Check the connector status for both the NA series and the expansion module.
  • B
    brownmatthewSep 6, 2025
    Why is MOD LED red on BeiJer I/O Systems?
    • E
      Erica LarsonSep 6, 2025
      If the MOD LED is red on your BeiJer I/O Systems, this could be due to a wrong address ID or a critical error in the firmware. Contact the sales team and send the module for repair.
  • J
    Jennifer GravesSep 9, 2025
    What causes MOD LED to flash green on BeiJer I/O Systems?
    • N
      Noah CaseySep 9, 2025
      If the MOD LED flashes green on your BeiJer I/O Systems, it indicates a failure of initialization EEPROM parameter. Contact the sales team and send the module for repair.