Function
23
IRDH275BM-7_D00123_06_M_XXEN/07.2018
Function input F1/F2 to switch over to the standby mode
When the input terminals F1/F2 are bridged, the measuring function is
stopped and the message "STANDBY" appears on the display. The currently
measured value is blanked and the value > 10 MΩ is indicated. The alarm re-
lays and alarm LEDs no longer provide alarm messages. After opening the
function input F1/F2, a completely new measuring cycle for insulation moni-
toring is started.