Operation and setting
50
IRDH275BM-7_D00123_06_M_XXEN/07.2018
5.9 Menu SERVICE
This menu item is provided for the Bender service personnel and is protected
by a password against erroneous settings. It is intended to provide fast fault
clearance by qualified experts in the event of a device error.
5.10 Parameterization via Internet
The parameters of the ISOMETER® indicated below can be checked and set
from a remote place of use by using a personal computer. In addition, a brows-
er (viewing program for Internet application) and our protocol converter
FTC470XET (BMS <==> Ethernet/TCP/IP) are required.
Remote setting is possible for:
Response value Alarm 1 (100…10,000 kΩ)
Response value Alarm 2 (100…10,000 kΩ)
Operating principle alarm relay K1 (e.g. N/O operation)
Operating principle alarm relay K2 (e.g. N/O operation)
Current output ranges for external measuring instruments
(0/4…20 mA)
Maximum system leakage capacitance (2 µF or 5 µF)
Time for repetition of the automatic self test (off/ 1 h/ 24 h
Starting time of the automatic self test (0.00…23.00 h)
Language of the alarm messages to be displayed (D, GB)
Setting the fault memory to ON or OFF