Technical data IRDH275BM-7 with AGH675S-7…
61
IRDH275BM-7_D00123_06_M_XXEN/07.2018
7.3 Data in tabular AGH675S-7
Insulation coordination in consideration of IEC 61800-5-1:2003
Rated voltage......................................................................................................................................................AC 7.2 V
Voltage test in consideration of IEC 61800-5-1:2003
Type test:
Rated impulse voltage (basic insulation)............................................................................................................... 40 kV
AC voltage test (basic insulation)........................................................................................................................... 20 kV
Partial discharge test ..............................................................................................................................................14 kV
Routine test:
AC voltage test ........................................................................................................................................................40 kV
Voltage ranges
Nominal voltage range U
n
................................................................................................. AC, 3(N)AC, DC 0…7.2 kV
Nominal frequency f
n
.................................................................................................................................... 0…460 Hz
Environment/EMC
Operating temperature (normal operation)............................................................................................-10…+60 ºC
Operating temperature (continuous operation with asymetrical earth fault)........................................-10…+55 ºC
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ............................................................... 3K5 (no condensation, no formation of ice)
Transport (IEC 60721-3-2)....................................................................... 2K3 (no condensation, no formation of ice)
Long-term storage (IEC 60721-3-1)........................................................ 1K4 (no condensation, no formation of ice)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ........................................................................................................3M4 (3M7 Y shaft)
Transport (IEC 60721-3-2)....................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1)........................................................................................................................ 1M3
Connection
Connection terminal 2 (medium voltage)............................... high-voltage cable (encapsulated on the device side)
Connection, flexible with ring terminal ............................................................................................................. M4
Connection terminal 3, 4, 5.......................................................................................................... screw-type terminals
Connection, rigid, flexible.............................................................................................. 0.2…4 mm
2
/0.2…2.5 mm
2
Connection, flexible with connector sleeve .......................................................................................... 0.25...2.5 mm
2