4. Installation and connection
4.1 Installation of the coupling device AGH675S-7…
For operation the coupling devices have to be installed into a "closed
electrical operating area", refer to IEC 61800-5-1:2003
The coupling device is to be installed in a place where the pollution
degree to be expected is ≤ 2, refer to IEC 61800-5-1: 2003, subclause
4.2.6.2.2
An "Enclosure suitable for high voltage areas" has to be selected for ins-
tallation, refer to IEC 61800-5-1: 2003
The high voltage connection cable must not be directly routed on con-
ductive surfaces that are connected to earth. This avoids partial
discharges and prevents damage to the insulation of the high voltage
cable between the AGH and the system to be monitored!
Either additional insulation layers are required or a clearence of
≥ 10 cm between the cable and the conductive surfaces has to be pro-
vided.
Danger of electric shock!
The coupling device is operated with voltages above 1000 V,
which can be life-threatening in case of direct contact. Make
sure that only electrically skilled persons work on or with the
device. Read the operating manual of the coupling device
carefully.