Serial interfaces
56
IRDH275BM-7_D00123_06_M_XXEN/07.2018
BMS-bus address ranges
Addresses* Device Meaning
0 There is no device with address 0 !
Information sent to address 0 applies to all
devices connected to the interface (broadcast)
1 PRC1470 Control and indicating device
1…30 IRDH275B/
375B/575
Insulation monitoring device
1…30 FTC470… Protocol converter
2…30 EDS47x-12 Insulation fault evaluators (localisation)
31…60 SMO480-12 Signal converter relay
61…90 EDS47xE-12 Insulation fault evaluators (localisation)
111…119 PGH47x Test device for insulation fault location
121…150 PGH47xE Test device for insulation fault location
Malfunctions due to wrong address assignment!
Assigning wrong addresses to external devices may cause
malfunctions.
Assign the addresses in a way that there are no gaps of more
than five subsequent addresses (1…30, 31…60, 61…90,
111…119 and 121...151).