Product description
14
COM465IP-COM465DP_D00216_02_M_XXEN/03.2017
Setting internal parameters and the configuration of Bender Universal measuring instruments
and energy meters.**
Time synchronisation for all assigned devices
History memory (1,000 entries)
Data logger, freely configurable (30 * 10,000 entries)
Documenting the device: A PDF file to document the settings of the used COMTRAXX device
can be generated.
A backup file with all settings of the used COMTRAXX device can be generated and imported.
50 data points from third-party devices (via Modbus RTU or Modbus TCP) can be integrated into
the system.
A virtual device with 16 channels can be created.
*) Displaying the parameters of BMS bus devices is only possible if the gateway is connected to the in-
ternal BMS bus.
**) Individual parameters can be set via a web-based application and externally (via BMS/ICOM/BCOM),
but NOT via Modbus or PROFIBUS. Only parameter assigned devices can be read; in order to change
settings, function module C is required!
Additional to COM465DP only:
Support for external applications (e.g. visualisation programs or PLCs) by means of the PROFI-
BUS DP protocol.
Reading the latest measured values, status and alarms messages from all assigned devices. Uni-
form access to all assigned devices by means of PROFIBUS DP via integrated servers.
Control commands: From an external application (e.g. visualisation software or PLC), com-
mands can be sent to devices by means of PROFIBUS DP.
3.2.2 Function module A
Allocation of individual texts for devices, channels (measuring points) and alarms.
Device failure monitoring
E-mail notification in the event of alarms or system faults to different users.
Configuration of e-mail notifications.
Documenting the device: A PDF file to document the settings of any device in the system can
be generated.
Documenting the system: A PDF file to document the settings of all devices in the system can
be generated.
3.2.3 Function module B
Supports external applications (e.g. visualisation programs or PLCs) by means of the Modbus
TCP protocol
Reading the latest measured values, status and alarms messages from all assigned devices. Uni-
form access to all assigned devices by means of Modbus TCP via integrated servers.
Control commands: From an external application (e.g. visualisation software or PLC), com-
mands can be sent to devices by means of Modbus TCP.
Access to alarms and measurement values via SNMP protocol (V1, V2c or V3).