Product description
17
COM465IP-COM465DP_D00216_02_M_XXEN/03.2017
3.6 Description of function
3.6.1 Interfaces
COM465… communicates with the devices and systems assigned via various interfaces:
BMS (RS-485) for Bender systems such as EDS46x/49x, RCMS46x/49x and MEDICS. COM465…
can be operated as a master or as a slave. Requests are answered more quickly on operation of
the COM465… as a master. The COM465… can be operated on the internal and external BMS
bus.
BCOM for new and future Bender systems, e.g. ISOMETER® iso685-D.
Modbus RTU (RS-485) COM465… on operation as a master for Bender universal measuring
devices PEM..3 and also PEM..5 with restricted functionality (full functionality of PEM..5 only via
Modbus TCP).
Modbus TCP (Ethernet) for Bender universal measuring devices PEM..5
COM465DP only: coupling with PROFIBUS DP. For this purpose the gateway is connected to the
PROFIBUS DP network as a PROFIBUS DP slave.
120 Ω
A B A B A B
max. 1200 m
BA
120 Ω
BMS bus
LAN
Web-
Browser
Internet
Firewall
PC1 PC2
PC3
Web-
Browser
TCP/IP via ISDN, DSL, ...
TCP/IP via Ethernet
RJ45
10/100 Mbit/s
RS485
Modbus/TCP
Modbus/TCP
Client
OPC
Modbus/TCP
BACnet
max. 1200 m
PROFIBUS-DP (nur COM465DP)
PROFIBUS-
Slave
PROFIBUS-Master
PROFIBUS-
Slave
PROFIBUS-
Slave
COM465…
BA
120 Ω
120 Ω
A B A B
max. 1200 m
Modbus/RTU
PEM..3 PEM..5*
PEM..5*iso685...