61
COM465IP-COM465DP_D00216_02_M_XXEN/03.2017
8. Technical specifications
8.1 Tabular data
( )* = Factory setting
Insulation coordination in acc. with IEC 60664-1/IEC 60664-3
(For 230 V variants B95061060)
Rated voltage........................................................................................................................................................ AC 250 V
Rated impulse withstand voltage/overvoltage category ......................................................................................4 kV / III
Pollution degree ................................................................................................................................................................ 3
Safe isolation (reinforced insulation) between
...............................................................(A1/+, A2/-) - [(AMB, BMB), (ABMS, BBMS), (X2), (X3, X4), (PROFIBUS DP)]
Insulation coordination in acc. with IEC 60664-1/IEC 60664-3
(For 24 V variants B95061061)
Rated voltage........................................................................................................................................................... AC 50 V
Rated impulse withstand voltage/overvoltage category .................................................................................. 0.5 kV / III
Pollution degree ................................................................................................................................................................ 3
Supply voltage
Supply voltage U
s
................................................................................................................................... See ordering data
Tolerance of U
s
.............................................................................................................................................. -20…+15 %
Frequency range U
s
................................................................................................................................ See ordering data
Power consumption .............................................................................................................................. See ordering data
Indications
LEDs:
ON .........................................................................................................................................................Operation indicator
PROFIBUS .....................................................................................................................................PROFIBUS DP data traffic
BCOM .......................................................................................................................................................BCOM data traffic
MODBUS ................................................................................................................. Modbus TCP/Modbus RTU data traffic
BMS ............................................................................................................................................................ BMS data traffic
Ethernet (terminal X2) ................................ Illuminates if connected to the network, flashes during data transmission
Memory
E-mail configurations (function module A only) and device failure monitoring ...................................max. 250 entries
Individual texts (function module A only) ..................................... unlimited number of texts each with 100 characters
Number of data points for "third-party devices" on the Modbus TCP and Modbus RTU.............................................. 50
Number of data loggers ................................................................................................................................................... 30
Number of data points per data logger ....................................................................................................................10,000
Number of entries in the history memory ..................................................................................................................1,000
Data display
Number of pages.............................................................................................................................................................. 20
Background image size ................................................................................................... 50 kByte (scaled down if larger)
Data points (per page) .....................................................................................50 devices or channels, 150 text elements
Interfaces
Ethernet
Connection ................................................................................................................................................................... RJ45
Data rate ....................................................................................................................................10/100 MBit/s, autodetect
DHCP ............................................................................................................................................................... on/off (off)*