Technical specifications
62
COM465IP-COM465DP_D00216_02_M_XXEN/03.2017
toff (DHCP................................................................................................................................................. 5…60 s (30 s)*
IP address ................................................nnn.nnn.nnn.nnn, can always be reached via (192.168.0.254*, 169.254.0.1)
Netmask ........................................................................................................................ nnn.nnn.nnn.nnn (255.255.0.0)*
Protocols (depending on function module selected) ..................TCP IP, Modbus TCP, Modbus RTU, DHCP, SMTP, NTP
SNMP
Versions.....................................................................................................................................................................1, 2c, 3
Devices supported........................................................Queries to all devices (channels) possible (no trap functionality)
BMS bus (internal/external)
Interface/protocol ...................................................................... RS-485/BMS internal or BMS external (BMS internal)*
Operating mode ............................................................................................................................master/slave (master)*
Baud rate BMS ........................................................................................................................................ Internal 9.6 kbit/s
............................................................................................................................................external 19.2; 38,4; 57.6 kBit/s
Cable length ....................................................................................................................................................... ≤ 1200 m
Cable: Twisted pair, shielded, one end of shield connected to PE .......................... Recommended: J-Y(St)Y min. 2x0.8
Connection ............................................................................................................................................. X1 (ABMS, BBMS)
Connection type ............................................................................................... See connection "Push-wire terminal X1"
Terminating resistor .................................................................................120 Ω (0.25 W), can be switched on internally
Device address, BMS bus internal/external .................................................................................................... 1…99 (1)*
BCOM
Interface/protocol .......................................................................................................................................Ethernet/BCOM
BCOM system name........................................................................................................................................... (BENDER)*
BCOM subsystem address................................................................................................................................ 1…99 (1)*
BCOM device address....................................................................................................................................... 1…99 (1)*
Modbus TCP
Interface/protocol ........................................................................................................................... Ethernet/Modbus TCP
Operating mode .................................................................................. Client for PEM and "third-party devices" assigned
Operating mode .................................................Server for access to process image and for Modbus control commands
Modbus RTU
Interface/protocol .............................................................................................................................. RS485/Modbus RTU
Operating mode ....................................................................................................................................................... Master
Baud rate ................................................................................................................................................ 9.6…57.6 kBit/s
Cable length ....................................................................................................................................................... ≤ 1200 m
Connection ................................................................................................................................................. X1 (AMB, BMB)
Connection type ............................................................................................... See connection "Push-wire terminal X1"
Terminating resistor .................................................................................120 Ω (0.25 W), can be switched on internally
Supported Modbus RTU slave addresses .............................................................................................................. 2…247
PROFIBUS DP (COM465DP only)
Interface/protocol RS-485 .............................................................................................electrica
lly isolated/PROFIBUS DP
Operating mode ......................................................................................................................................................... Slave
Baud rate .................................................................................. Automatic baud rate detection: 9.6 kbit/s…1.5 Mbit/s
.............................................................................................................9.6 / 19.2 / 93.75 / 187.5 / 500 kbit/s , 1.5 Mbit/s
Connection ....................................................................................................................................................... Sub D 9-pin
Device address, PROFIBUS DP........................................................................................................................ 1…125 (3)*
Environment / EMC
EMC .................................................................................................................................................................. EN 61326-1
Ambient temperatures:
Operating temperature ............................................................................................................................... -25…+55 °C
Transport ..................................................................................................................................................... -40…+85 °C
Long-term storage ...................................................................................................................................... -25…+70 °C