Loading...
PROFIBUS DP (COM465DP only)
36
COM465IP-COM465DP_D00216_02_M_XXEN/03.2017
Response from the gateway:
For an explanation of the protocol structure see "Type 1: Querying measured data from devices on
the bus" on page 27.
Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 8 Byte 9
ID
Data
value
high
high
Data
value
high
low
Data
value
low
high
Data
value
low
low
Alarm
& test
Range
& unit
Descrip-
tion high
Descrip-
tion low
0xFF
0x03 0x42 0xCC 0x00 0x00 0x02 0x1E 0x00 0x66 0xFF
Byte 0: Sequential ID no.
Byte 1-4: Floating point value = 102 (earth connection)
Byte 5: Alarm type and test type = 0x02 (device fault)
Byte 6:
Structure of the byte: Range and unit = 0x1E (code)
Byte 7-8: 0x66 = Earth connection
Byte 9: 0xFF

Table of Contents