7.3.26 D_IMD_ERROR_CODE
This data value represents the IMC and VIFC error codes in the error frame.
IMC error codes
Value Description
32 Timeout 10 ms (incomplete frame)
33 Checksum error detected in frame
34 Invalid parameter
35 Unknown command
36 Error in EEPROM access
37 Repeated or missing frame
VIFC error codes
Value Description
1000 Command locked
1001 Queue full (Command rejected)
1002 Command unavailable (Measurement Off)
1032 Timeout 10 ms (incomplete frame)
1033 Checksum error detected in data frame
1034 Invalid parameter
1035 Unknown command
1037 Repeated or missing data frame
1038 No response (Timeout 60 ms)
1039 Communication error
1040 Invalid IMC response command
7.3.27 D_IMD_FAILED_CMD
This data value represents the frame command identification of a failed IMC command.
Value Description
0 ... 255 Every CMD sent in a request to the IMD