Technical data
15. Technical data
15.1 Tabular data iso1685Dxx
( )* = Factory settings
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Insulation coordination according to IEC 60664-1
Rated voltage..............................................................................................................................................................................DC 1500 V
Overvoltage category (OVC)..................................................................................................................................................................... III
Rated impulse withstand voltage ...................................................................................................................................................... 8 kV
Rated insulation voltage...................................................................................................................................................................1500 V
Pollution degree exterior.......................................................................................................................................................................... 3
Voltage test, routine test (IEC 61010-1) ......................................................................................................................................... 2.2 kV
Voltage ranges
Nominal system voltage range U
n
iso 1685DP.................................................................................... AC 0…1000 V / DC 0…1500 V
Tolerance of U
n
iso1685DP......................................................................................................................................AC +10 % / DC +5%
Nominal system voltage range U
n
iso1685D-HV................................................................................ AC 0…2000 V / DC 0…3000 V
Tolerance of U
n
iso1685D-HV............................................................................................................................................................+5%
Frequency range of U
n
..................................................................................................................................................... DC, 1…460 Hz
Supply voltage U
s
(see also device nameplate) ................................................................................................................. DC 18…30 V
Frequency range of U
s
........................................................................................................................................................................... DC
Power consumption ....................................................................................................................................................................... 9 W
Measuring circuit for insulation monitoring
Measuring voltage U
m
(peak value)............................................................................................................................................... ±50 V
Measuring current I
m
(at R
F
= 0 Ω)........................................................................................................................................... 1.5 mA
Internal DC resistance R
i
...............................................................................................................................................................
70 kΩ
Impedance Z
i
at 50 Hz.................................................................................................................................................................. 70 kΩ
Permissible extraneous DC voltage U
fg
................................................................................................................................. DC 1500 V
Permissible system leakage capacitance C
e
.......................................................................................... profile dependent, 0…2000 µF
Measuring range leakage capacitance ................................................................................................................................20…2000 F
Tolerance measurement of C
e
........................................................................................................................................... ±10 % ±10 µF
Frequency range measurement of C
e
............................................................................................................................ DC, 30…460 Hz
Response values for insulation monitoring
Response value R
an1
(alarm 1) ........................................................................................................................... 200 Ω…1 MΩ
(
40
kΩ
)*
Response value R
an2
(alarm 2) ........................................................................................................................... 200 Ω…1 MΩ
(
10
kΩ
)*
Condition response value ........................................................................................................................................................R
an1
R
an2
Upper limit of the measuring range when set to C
emax
= 2000 µF ............................................................................................... 50 kΩ
Upper limit of the measuring range when set to C
emax
= 500 µF ................................................................................................ 200 kΩ
Relative uncertainty (10 kΩ…1 MΩ) (acc. to IEC 61557-8)........................................................................................................ ±15 %
Relative uncertainty (0.2 kΩ…< 10 kΩ)....................................................................................................................... ±200 Ω
±15 %
Hysteresis ........................................................................................................................................................................................... 25 %
Time response
Response time t
an
at R
F
= 0.5 x R
an
(R
an
= 10 kΩ) and C
e
= 1 F acc. to IEC 61557-8 ...........................................................................
profile dependent, typ. 10 s
Measuring circuit for insulation fault location (EDS) (only iso1685DP)
Locating current I
L
DC ................................................................................................................................................................. 50 mA
Test cycle/pause .............................................................................................................................................................................. 2 s/4 s
Indication
Display................................................................................................................................. graphic display 127 x 127 pixel, 40 x 40 mm
Display range measured value ........................................................................................................................................ 0.2 kΩ…50 MΩ
LEDs
ON (operation LED)............................................................................................................................................................................ green
PGH ON..............................................................................................................................................................................................yellow
SERVICE .............................................................................................................................................................................................yellow
ALARM 1 ...........................................................................................................................................................................................yellow
ALARM 2 ...........................................................................................................................................................................................yellow
Digital inputs
Operating mode, adjustable................................................................................................................................... active high, active low
Functions.....................................................................................................none, test, reset, deactivate device, insulation fault location
High level ................................................................................................................................................................................. 10…30 V
Low level .................................................................................................................................................................................... 0…0.5 V
Serial interface
Interface/protocol ................................................................................................................................................................. RS-485/BMS
Connection............................................................................................................................................................................ terminals A/B
Cable length .............................................................................................................................................................................. ≤ 1200 m
Shielded cable (shield to functional earth on one end) ............................................................... 2-core,
³0.6 mm
2
, e.g. J-Y(St)Y2x0.6
Shield.......................................................................................................................................................................................... terminal S
Terminating resistor, can be connected (Term. RS-485).................................................................................................. 120 Ω (0.5 W)
Device address, BMS bus ................................................................................................................................................ (1) 2…90 ( 2)*

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER iso1685D Series and is the answer not in the manual?

Bender ISOMETER iso1685D Series Specifications

General IconGeneral
BrandBender
ModelISOMETER iso1685D Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals