Function
3. Function
3.1 Features
Insulation monitoring of IT systems up to
iso1685DP-425 AC 1000 V/DC 1500 V
iso1685D-HV-425 AC 2000 V/DC 3000 V
Measurement of low-resistance insulation faults
Separately adjustable response values R
an
1 (alarm 1) and R
an
2 (alarm 2)
(both 200 …1 M) for prewarning and alarm
High-resolution graphic LC display for excellent readability and recording of the
device status
Automatic adjustment to high system leakage capacitances, selectable range
Connection monitoring
Integrated locating current injector up to 50 mA for insulation fault location
(only iso1685DP)
Device self test with automatic message in the event of a fault
Alarm relays separately adjustable for insulation faults and device errors
RS-485 interface (BMS bus), e.g. for controlling insulation fault location
The integrated µSD card slot cannot be used. The device does not store any data on
the µSD card.
3.2 Product description
The ISOMETER® iso1685Dxx is used for insulation monitoring of extensive IT systems up
to AC 1000 V/DC 1500 V or AC 2000 V/DC 3000 V. The specially developed measurement
method monitors the insulation resistance also in installations where extremely high sys-
tem leakage capacitances against earth exist due to interference suppression methods.
Adaptation to system-related high leakage capacitances also occurs automatically.
The ISOMETER® iso1685Dxx generates locating current pulses required for insulation
fault location. That allows the localisation of the insulation fault using permanently in-
stalled or mobile insulation fault locators.
3.3 Function description
Insulation monitoring is carried out using an active measuring pulse which is superim-
posed onto the IT system to earth via the integrated coupling. When the insulation resist-
ance between the IT system and earth falls below the set prewarning response value
R
an
1, the “ALARM 1” LED lights and the relay K1 (11/12/14) switches. When the insulation
resistance falls below the alarm response value R
an
2, the alarm relay K2 (21/22/24) switch-
es and the “ALARM 2” LED lights.
The locating current injector integrated in the device for insulation fault location is acti-
vated externally via the BMS interface. When starting the insulation fault location, the LED
“PGH ON” signals the locating current pulse.
The ISOMETER® cannot take over the master function. If there is no master in the system,
the device can act as a backup master and communicate with the slaves in the system.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Bender ISOMETER iso1685D Series and is the answer not in the manual?

Bender ISOMETER iso1685D Series Specifications

General IconGeneral
BrandBender
ModelISOMETER iso1685D Series
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals