Modbus register assignment of the ISOMETER®
47
isoPV425_D00028_09_M_XXEN/05.2018
3016 RW Baud rate "Adr 1" UINT 16 ---
0 = BMS
1 = 1.2 k
2 = 2.4 k
3 = 4.8 k
4 = 9.6 k
5 = 19.2 k
6 = 38.4 k
7 = 57.6 k
8 = 115.2 k
3017 RW Parity "Adr 2" UINT 16 ---
0 = 8N1
1 = 8O1
2 = 8E1
3018 RW
Start-up delay "t"
during device start UINT 16 s 0 …10
3019
RW Response delay
"ton" for relays
"K1" and "K2"
UINT 16 s 0 … 99
3020 RW
Delay on release
"toff" for relays
"K1" and "K2"
UINT 16 s 0 … 99
3021 RW
Repetition time
"test" for auto-
matic
device test
UINT 16 ---
0 = OFF
1 = 1
2 = 24
3022 RW Reserved --- --- ---
3023 RW Reserved --- --- ---
3024 RW
Test of the system
connection dur-
ing device test
"nEt"
UINT 16 ---
0 = Inactive
1 = Active
Register
Property Description Format
Unit
Value range

Table of Contents