Bennett 3000 Spec 300 Series Instruction Manual Dispenser Operation
32
SUGGESTED SETUP SEQUENCE
The software program for each new dispenser shipped from the factory is pre-programmed with the default settings in some of the Menu
Codes. Make sure the initial setup menu codes are programmed before testing any dispenser operations. Failure to do so may lead to
difficulty getting the dispenser to operate properly.
INITIAL SETUP
Menu Code
Initial Setup
Default Setting
3
Managers Access Code
2218
7
Pump Type
Sides = 2, Grades = 1, Hoses = 1, Tier = 1
4
Pricing For each hose and 1 or 2-tier pricing
0000
21
Communication Type (Current Loop, Stand Alone, RS485,
Generic Current Loop, Fleet RS485)
0 = Console Mode
22
Dispenser Address (Only used for Generic Current Loop & RS485)
0 = Only one dispenser on the communications
loop
27
Meter (Electronic) Calibration
0.00
REMAINING DISPENSER SETUP
Menu Code
Remaining Dispenser Setup
Default Setting
5
Meter Value Amount for each meter
6
Programming Selections Viewer
8
Decimal Location For other than U.S. Standard
0 = U.S.A.
9
No Flow Time Out ( International Purposes Only)
--- = Infinite Time
10
Slow Flow Amount Control for Prepay Sales
0.100 Volume Unit
11
Volume Allocation for a sale at a pump (International Use Only)
0999 Volume Units
12
Pre-Charge, Idle, Last Sale, and Handle State Timer
Pre-Charge = 2 seconds, Last Sale = 30, Idle = 15,
Handle State = 0
14
Price Display Control Operation
0 = Flashing, 0 = Dash, Flip = 0
15
Fleet System Interface Compatibility
0 = No Fleet Interface
16
Battery Timeout
30 Seconds
17
Local Preset - Operation
0 = No Preset
18
Motor Delay Suction Pumps
0 = No Delay
20
Masked Volume
.010 gallons or .10 liters
24
Solenoid Valve Type
2 = Proportional Valve
28
Rounding or Truncating the Sale Amount (International Use Only)
1 = Rounding the Sale Amount
30
Real Time Clock
(YY/MM/DD/HH:MM)
31
Total Access
1 = Access allowed without manager password
37
ATC Petroleum Commodity Group
0 = Long
50
Pulse Output Pulse Unit, Pulse Ratio, and Pulse Speed (PPS)
0 = Disabled
60
End Condition Prepay Sale
0 = Cash Drawer
70
Marina Pulser Enable Delay
0 Seconds
96
Proportional Valve (Start of Sale or End of Prepay / Preset Sale
Start of Sale = 35 %, End of Prepay Sale = 35 %
99
Unit of Measure - (International Purposes Only)
1 = Gallons, 1 Decimal position 3 places