TEBEVERT III INVERTER SYSTEM (120 VDC)
07.11.2011 26 028-0009-006
3.7 AC DISTRIBUTION PANEL
External AC electrical panels are recommended. These can be sourced
from your local electrical supplier Benning. Two additional AC distribution
options can be used with the inverter cabinet. One utilizes a standard
North American style snap-in breaker and the other utilizes standard DIN
style breakers.
3.7.1 NA STYLE SNAP-IN BREAKER PANEL
Note: This panel cannot be installed in the inverter cabinet.
This AC Distribution Panel is a UL Listed, externally mountable option.
The panel is designed to accommodate up to 20 breaker positions using
standard Eaton/Cutler Hammer CH style snap-in breakers. The maximum
allowable sized breaker is 50A per pole. The maximum allowable current
per bus is 125A. The AC Distribution Panel is designed to mount into a
standard 19” relay rack and occupy 5U of vertical space. Conduit
knockouts are provided for conduit to enter the back of the panel for the
output wiring. These knockouts sized for either ¾” or 1” conduits. The
input wiring is provided via a pigtail through a knockout also located at the
rear of the panel. This panel can be wired to the inverter output. This
option can be wired as 120VAC and Neutral or 120/240VAC and Neutral
depending on the output voltage option selected.
Ground Bar
Main Lugs CH Breaker
Positions