EasyManua.ls Logo

bluelab Pro Controller Wi-Fi - Page 14

bluelab Pro Controller Wi-Fi
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Temperature required / alarms
Temperature is difficult to maintain at a
constant level using on and off times, so the
Bluelab Pro Controller manages it differently to
conductivity and pH.
It is normal practice to set the temperature on
time to ‘continuous’, which allows the
heater/cooler to operate until the ‘temperature
off’ value is reached.
For example, if you are heating a tank or
reservoir, when the “temperature on” value is
reached, heating will be turned on. When the
“temperature off” value is reached, it will be
turned off.
Alarm
and Required
‘Quick
-
set’
Use the Quick-set features to quickly set therequired”,alarm highandalarm low
values for all three measurements. The alarm values are taken from the actual
readings, so ensure your system is stable before using the Quick-set function.
1.
In ‘Required / Alarms’ mode
select the measurement you
want to ‘quick-set’.
2. Press the alarm button.
3. Quick-set only sets the required
and alarm vales for the selected
measurement, so repeat steps 1
& 2 for the other measurements
required.
This table shows the values that are
applied when ‘quick-set’ is used.
‘Quick-set’ Alarm Values
Alarm Low Required Alarm High
Conductivity
Actual value –
0.2 EC / 2 CF
100 TDS
140 ppm
Actual
value
Actual value +
0.2 EC / 2 CF
100 TDS
140 ppm
Temperature
Actual value –
3°C / 5 °F
Actual
value
Actual value +
3°C / 5 °F
pH
Actual value –
0.5pH
Actual
value
Actual value +
0.5pH
24
Al.h
1
Temperature off
value
Temperature on
value
Al.l0
30
26
22
Alarm high value
Alarm low value
Temperature Control Off
Temperature Control O
n
Temperature Control O
26°C
24°C
16°C
If using a Temperature
Lower/Cooling Device
If using a Temperature
Raise/Heating Device

Related product manuals