4 Technical Data
4.1 General technical data
CE conformity
The frequency inverters ACU
meet the requirements of the low voltage directive
2006/95/EEC and EN 61800-5-1.
EMC directive
For proper installation of the frequency inverter in order to meet the require-
ments of EN
61800-3,
please comply with the installation instructions in these
operating instructions.
Interference
immunity
The frequency inverters ACU meet the requirements of EN 61800-3 for use in
industrial environments.
UL Approval
The frequency inverters marked with the UL label according to UL508c also meet
the requirements of
the CSA Standard C22.2-No. 14.
UL a
p
proved are the device series ACU401 in sizes 1 to 7 and ACU201 devices in
sizes 1 and 2.
Safety function
The function is described in the application manual “Safe Torque Off”.
Ambient
temperature
Operation: 0…55 °C; as from 40 °C power reduction has to be considered.
Environmental
class
Operation: 3K3 (EN60721-3-3)
Relative humidity 15…85 %, no water condensation.
Degree
of protection
IP20 if covers and connection terminals are used properly.
Altitude
of installation
Up to 1000 m at rated specifications.
Up to 4000 m at reduced power.
Storage
Storage according to EN 50178.
BONFIGLIOLI VECTRON recommends that the unit be connected to mains volt-
age for 60 minutes after one year, at the latest.
Overload capability
Continuous Operation: 100 % I
N
Up to 150 % I
N
for 60 s
Up to 200 % I
N
for 1 s
Devices
-01, -03
(0.25 & 0.37 kW):
Up to 200 % I
N
for 60 s
Up to 200 % I
N
for 1 s
The overload capability can be used once in a time cycle of 10 minutes.
Functions
Control methods adjusted to motors and application (configuration).
Adjustable speed/torque control.
Various control functions for motor and frequency inverter.
Positioning absolute or relative to a reference point.
Search Run.
Special brake control and load detection for lifting gear.
S-ramps for jerk limitation during acceleration and deceleration.
Technology (PI) controller.
Parameterizable Master-Slave operation via system bus.
Error memory.
Simplified and extended control via PC (commissioning, parameterization,
data set backup, diagnosis with Scope).
Parameterization
Freely programmable digital inputs and outputs.
Various logic modules for linking and processing of signals.
Four separate data sets incl. motor parameter.
30 Operating Instructions ACU
06/13

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the BONFIGLIOLI ACTIVE Cube ACU 201-11 and is the answer not in the manual?

BONFIGLIOLI ACTIVE Cube ACU 201-11 Specifications

General IconGeneral
BrandBONFIGLIOLI
ModelACTIVE Cube ACU 201-11
CategoryInverter
LanguageEnglish

Related product manuals