8.2.4 Machine Data
The machine data to be entered during the guided commissioning procedure are indi-
cated on the type plate or the data sheet of the motor. The factory settings of the
machine parameters are based on the nominal data of the frequency inverter and the
corresponding four-pole three-
phase motor. The entered and calculated machine data
are ch
ecked for plausibility during the guided commissioning procedure. The user
should verify the factory-set rated data of the three-phase motor.
U
FUN,
I
FUN,
P
FUN
are rated values of the frequency inverter.
370 Rated voltage
0.17â‹…U
2â‹…U
U
• Use the arrow keys to select the required parameter and edit the parameter val-
ue.
• Use the ENT key to confirm the selected parameter and the parameter values
The rated data of the motor are to be entered according to the specifications on the
rating plate for the motor connection type used (star or delta connection).
If the data entered deviate from the rating plate, the parameters will not be identified
correctly. Parameterize the rated data according to the rating plate of the motor for
the wiring of the motor winding. Consider the increased rated current of the connect-
ed three-phase motor.
BONFIGLIOLI BN 90LA Motor
06/13 Operating Instructions ACU 105