2306/05
8.5.5 0x6046/n Velocity min max amount
he ob
ect velocity min max amount comprises the subindex 01 = velocity min
amount and subindex 02 = velocity max amount.
Velocity min max amount
Index Subindex Meaning Value
0x6046 0 Number of entries (unsigned 8) 2
1 Velocity min amount (RPM) (unsigned 32)
2 Velocity max amount (RPM) (unsigned 32)
The velocity min amount variable corresponds with the parameter value
inimum
Frequency
418 in the first data set. The specification is done in the unit RPM (only
positive values) and is converted internally to a frequency, takin
the ob
ect pole
number into account. The value is not stored and is set back to zero after the reset.
The value for the object velocity max amount is written internally onto the parameter
value
Maximum Frequency 419 in data set 1 in the form of a converted frequency.
After the reset, the ob
ject value velocity max amount is converted into the unit RPM
from the parameter
Maximum Frequency 419.
If the reference value with the object target velocity is specified smaller than the
ob
ect value velocity min amount or lar
er than velocity max amount, tar
et velocity is
internally limited to the values in question.
Parameter Setting
No. Object Min. Max.
0x6046/n
elocity min max amount 0 32767
Velocity max amount
Velocity max amount
Velocity min amount
Velocity min amount
Output
Input
Note:
he ob
ect velocity min amount is always set to the ob
ect value = 0 afte
the reset of the frequency inverter.